Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd

EK keeps looking for valuable distributors and partners around international markets…

Manufacturer from China
Active Member
10 Years
Home / Products / Air Cooled Modular Chiller /

Total Heat Recovery 130KW Air Cooled Modular Chiller

Contact Now
Guangdong EuroKlimat Air-Conditioning & Refrigeration Co., Ltd
City:dongguan
Province/State:guangdong
Country/Region:china
Contact Person:MrLENG Zhengliang
Contact Now

Total Heat Recovery 130KW Air Cooled Modular Chiller

Ask Latest Price
Video Channel
Brand Name :EuroKlimat
Model Number :EKAC460BR1SR
Certification :ISO9001, ISO14001, OHSAS18001, CRAA, CQC
Place of Origin :China
MOQ :1
Price :USD 200 per ton
Payment Terms :L/C, T/T
Supply Ability :3,000 pcs per month
Delivery Time :15 working days after received your payment
Packaging Details :Plywood
Type :air cooled
Voltage :380V/3/50HZ
Weight :1080 KG
Dimension(l*w*h) :2015mm*1150mm*2260mm
Cooling capacity :130 kw
Heating capacity :138 kw
Compressor type :scroll
Compressor :Copeland
Application :pharmaceutical, exhibition hall, office building, food, HVAC system , industrial process cooling
Evaporator type :Plate heat exchanger
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Totally Heat Recovery Air Cooled Modular Chiller 130KW

Features

1. Copeland scroll compressor or Danfoss scroll compressor
2. Plate heat exchanger / tank heat exchanger
3. Modular design , max 16 units work together
4. Industrial cooling application , and min -10 C outlet temperature
5. Outlet temperature control
6. Total heat recovery

The EKAC series total heat recovery modular air-cooled heatpump units introduce design and development essence of Europe total heat recovery technology, which perfectly combineair-cooled chiller and air source heat pump hot water unit. Inaddition to addressing cooling needs in summer and heatingneeds in winter, the unit can produce 40ºC to 50ºC domestichot water around the clock. It can replace hot water boilers,thus saving investment in hot water boilers and equipmentrooms. This can not only protect the environment, but alsosaves the operating cost. The unit can recover waste heatreleased from cooling, thus effectively avoiding “heat island effect" ;

Specifications:

Model: EKAC460
BR1SRM/S
Air conditioning mode Nominal cooling capacity kW 130
Nominal heating capacity kW 138
Total power of nominal cooling capacity kW 40
Nominal cooling operation current A 70.8
Total power of nominal heating capacity kW 40.4
Nominal heating operation current A 71.5
Water flow Nominal cooling capacity m³/h 22.4
Nominal heating capacity m³/h 23.7
Performance parameter W/W 3.25
Hot Water Mode Circular water flow m³/h 27.9
Nominal heating capacity kW 162
Total power of nominal
hot water provision capacity
kW 41.5
Cooling
+
Hot Water Mode
Nominal cooling capacity kW 119
Nominal heat recovery capacity kW 158
Total nominal power kW 39
Water flow Hot water m³/h 27.9
Chilled water at air conditioning side m³/h 22.4


Note:

■ Cooing capacity tested on : chilled water outlet temperature 7°C , water flow: 0.172m3/(h·kW),outdoor temperature 35 °C ;
■ Heating capacity: hot water outlet temperature 45°C ,water flow: 0.172m3/(h·kW) ,outdoor dry/web bulb temperature 7°C/6°C;

Inquiry Cart 0