Add to Cart
Features
1. Copeland scroll compressor or Danfoss scroll compressor
2. Plate heat exchanger or shell tube heat exchanger
3. Modular design , max 16 units work together
4. Industrial cooling application , and min -10 C outlet temperature
5. Outlet temperature control
6. EVI compressor fow low ambient temp , min -25 C ambient temperature for heating ;
7. Total heat recovery
The EKAC series total heat recovery modular air-cooled heatpump units introduce design and development essence ofEurope total heat recovery technology, which perfectly combineair-cooled chiller and air source heat pump hot water unit. Inaddition to addressing cooling needs in summer and heatingneeds in winter, the unit can produce 40ºC to 50ºC domestichot water around the clock. It can replace hot water boilers,thus saving investment in hot water boilers and equipmentrooms. This can not only protect the environment, but alsosaves the operating cost. The unit can recover waste heatreleased from cooling, thus effectively avoiding “heat island effect" ;
Specifications:
Model: | EKAC230 | |||
BR1SRM/S | ||||
Air conditioning mode | Nominal cooling capacity | kW | 68 | |
Nominal heating capacity | kW | 74 | ||
Total power of nominal cooling capacity | kW | 20.5 | ||
Nominal cooling operation current | A | 37.8 | ||
Total power of nominal heating capacity | kW | 21 | ||
Nominal heating operation current | A | 38.5 | ||
Water flow | Nominal cooling capacity | m³/h | 11.7 | |
Nominal heating capacity | m³/h | 12.7 | ||
Performance parameter | W/W | 3.32 | ||
Hot Water Mode | Circular water flow | m³/h | 14.1 | |
Nominal heating capacity | kW | 82 | ||
Total power of nominal hot water provision capacity |
kW | 20.5 | ||
Cooling + Hot Water Mode |
Nominal cooling capacity | kW | 64.5 | |
Nominal heat recovery capacity | kW | 84 | ||
Total nominal power | kW | 19.5 | ||
Water flow | Hot water | m³/h | 14.1 | |
Chilled water at air conditioning side | m³/h | 11.7 |
Note:
■ Cooing capacity tested on : chilled water outlet temperature 7°C , water flow: 0.172m3/(h·kW),outdoor temperature 35 °C ;
■ Heating capacity: hot water outlet temperature 45°C ,water flow: 0.172m3/(h·kW) ,outdoor dry/web bulb temperature 7°C/6°C;